Gabatarwa

A fannin watsa wutar lantarki mai ƙarfin lantarki mai ƙarfi, na'urorin canza wutar lantarki na 220kV suna taka muhimmiyar rawa wajen tabbatar da ingantaccen rarraba wutar lantarki. babban gibin rufitsakanin na'urorin juyawar wutar lantarki (transformer windings) suna wakiltar ɗaya daga cikin muhimman abubuwan ƙira, waɗanda ke shafar amincin na'urar juyawar wutar lantarki, tsawon rai, da kuma aikinta kai tsaye. A matsayinmu na shugabannin kasuwa a fasahar na'urorin juyawar wutar lantarki, mun fahimci cewa ƙirar rufin da ta fi dacewa tana da matuƙar muhimmanci wajen jure matsin lamba na wutar lantarki, gami da ci gaba da ƙarfin aiki, walƙiyar walƙiya, kuma sauyawar ƙaruwa.

Wannan labarin yana bincika hanyoyin nazarin filin lantarki masu inganci da dabarun ingantawa masu amfani don gibin babban rufin transformer 220kV tsakanin coil. Ta hanyar amfani da fasahohin kwaikwayo na zamani da ƙa'idodin ƙira masu ƙirƙira, za mu iya haɓaka aikin rufin transformer sosai, tare da tabbatar da ingancin aiki a cikin yanayi mafi wahala.

Muhimman Abubuwan Rufe Injin Canza Wutar Lantarki 220kV

Babban gibin rufin da ke tsakanin na'urorin juyawa masu ƙarfin lantarki na 220kV yana aiki a matsayin babban shingen dielectric, yana hana lalacewar wutar lantarki tsakanin na'urorin juyawa masu ƙarfin lantarki da ƙananan na'urori masu ƙarfin lantarki. Wannan tsarin rufin dole ne ya jure ba kawai yanayin aiki na yau da kullun ba har ma da nau'ikan na'urori daban-daban. yanayin overvoltageabubuwan da ke faruwa a lokacin rikice-rikicen grid.

A cikin aikace-aikacen 220kV, gibin rufin yawanci yana amfani da tsarin shinge mai yawawanda ya ƙunshi silinda ko naɗe-naɗen allon matsi waɗanda ke raba gibin zuwa ƙananan hanyoyin mai da yawa. Wannan hanyar tana ƙara inganta shi sosai. ƙarfin lantarki na farko na fitarwa na wani ɓangare(PDIV) kuma yana hana samuwar gadoji masu ƙazanta tsakanin naɗe-naɗen. Tsarin asali yana bin ƙa'idar "bututun takarda mai siriri, ƙaramin gibin mai", inda allon matse shinge yawanci kauri ne 2mm, kuma gibin mai tsakanin shingen yana tsakanin 6-10mm.

Rarraba filin lantarki a cikin waɗannan gibin ba abu ɗaya bane, tare da Yawan damuwayana faruwa a gefunan da ke lanƙwasawa, lanƙwasawa na jagoran jagora, da kuma hanyoyin haɗin rufi. Ba tare da ingantaccen tsari ba, waɗannan wurare masu tsananin damuwa na iya fara ayyukan fitar da iska daga waje, wanda ke haifar da raguwar rufin da kuma yiwuwar gazawa.

Dabaru na Binciken Filin Lantarki

Tsarin Ƙarfin Zane (FEM) Kwaikwayo

Tsarin rufin zamani ya dogara sosai akan nazarin abubuwa masu iyaka(FEA) don taswirar filin lantarki mai inganci. Ta hanyar rarraba yanayin rufin zuwa dubban abubuwa daban-daban, FEM na iya ƙididdigewa yiwuwar rarrabawakuma ƙarfin filintare da daidaito mai ban mamaki. Ga masu canza wutar lantarki na 220kV, wannan bincike yawanci yana mai da hankali kan muhimman yankuna uku: rufin saman, sashe na tsakiya tsakanin lanƙwasawa, kuma rufin ƙasa.

Kwaikwayon mu sun nuna cewa mafi girman ƙarfin filin lantarki a cikin na'urorin canza wutar lantarki na 220kV yawanci yana faruwa ne a lokacin da wutar lantarki ke aiki. kusurwoyin saman cikina na'urorin juyawa masu ƙarfin lantarki, musamman kusa da sassan ƙarshen layi. A lokacin gwajin walƙiya (1050kV don tsarin 220kV), waɗannan yankuna na iya fuskantar ƙarfin filin da ya wuce 8-9kV/mm, suna kusantar iyakokin lalata kayan rufi.

Gano Yankunan Damuwa Masu Muhimmanci

Ta hanyar cikakken nazarin filin lantarki, mun gano wasu muhimman wurare na damuwa da ke buƙatar kulawa ta musamman a cikin na'urorin canza wutar lantarki na 220kV:

  • Yankunan gefen da ke juyawa: Kusurwoyi masu kaifi a ƙarshen lanƙwasa suna haifar da babban yawan filayen, wanda ke buƙatar dabarun tantancewa na musamman.
  • Haɗi tsakanin rufin ƙarfi da ruwa: Abubuwan da ba su da alaƙa da dielectric na pressboard da mai suna haifar da ƙaruwar filin a hanyoyin haɗinsu.
  • Yankunan fita daga jagora: Wuraren sauyawa inda manyan hanyoyin wutar lantarki ke fita daga cikin na'urorin suna gabatar da rarrabuwar filin musamman masu ƙalubale waɗanda ke buƙatar nazarin girma uku.

Ga na'urorin canza wutar lantarki na 220kV, matsakaicin ƙarfin filin lantarki yawanci yana faruwa ne a cikin faifan farko kaɗan kusa da ƙarshen layi da kuma a wuraren haɗuwa tsakanin faifan da aka haɗa da na yau da kullun a lokacin yanayin motsawa. Waɗannan wurare suna buƙatar matakan kariya masu ƙarfi don hana lalacewa da wuri.

Dabaru na Ingantawa don Babban Gibin Rufewa

Ingantaccen Tsarin Geometric

Siffar lantarkiyana wakiltar ɗaya daga cikin dabarun da suka fi tasiri don inganta rarraba filin. Ta hanyar maye gurbin kusurwoyi masu kaifi da bayanan martaba masu lankwasada aiwatarwa toroidal electrodes, za mu iya rage ƙarfin filin har zuwa 30-40%. Ga masu canza wutar lantarki na 220kV, wannan ya haɗa da:

  • Zobba na ƙarshen tsaye(SER) a tashoshin naɗewa don ƙirƙirar santsi mai yuwuwar hawa.
  • Zoben kusurwatare da bayanan martaba waɗanda ke kusantar layukan kayan aiki, suna rage matsin lamba mai ƙarfi a saman allon matsi.
  • Maƙallan damuwaa cikin mahimman hanyoyin sadarwa don sarrafa bambance-bambancen filin da rage yawan taro.

Radius na inganta lanƙwasa yana da matuƙar muhimmanci - ƙara radius na kusurwar masu jagoranci da zobba masu tsauri na iya rage ƙarfin filin sosai (ƙarfin filin ∝ 1/radius).

Kayan Rufewa Masu Ci gaba

Zaɓin kayan aiki yana taka muhimmiyar rawa wajen inganta aikin rufin gida. Na'urorin canza wutar lantarki na 220kV ɗinmu suna amfani da:

  • Allon matsi mai yawatare da ingantaccen kwanciyar hankali da ƙarfin dielectric mafi girma.
  • Takardun da aka inganta a yanayin zafiwaɗanda ke ba da juriya mai kyau ga zafi, suna kiyaye halayen dielectric a yanayin zafi mai yawa.
  • Kayan da aka inganta nanocompositeinda nanoparticles (SiO₂, Al₂O₃) da aka ƙara a cikin epoxy ko mai suna inganta ƙarfin dielectric da kashi 20-30% yayin da suke haɓaka ƙarfin zafi.

Waɗannan kayan zamani suna ba da damar ƙarin ƙira mai ƙarfi na rufi yayin da suke kiyaye ko ma inganta iyakokin aminci. Misali, aiwatar da tsarin rufin nanocomposite na iya tsawaita rayuwar rufi da kashi 20-30% idan aka kwatanta da kayan gargajiya.

Tsarin Tsarin Rufewa

Inganta tsarin zahiri na abubuwan rufi yana haifar da ci gaba mai mahimmanci:

  • Tsarin rufin da aka ƙimainda kauri na rufi ya bambanta dangane da rarrabawar wutar lantarki a kan naɗewa.
  • Inganta sanya shingeta amfani da nazarin FEM don tantance mafi kyawun matsayi na allon bugawa wanda ke rage matsin lamba mafi girma na gibin mai.
  • Girman bututun maiwanda ke daidaita buƙatun wutar lantarki (ƙananan gibi don babban PDIV) tare da buƙatun sanyaya (isasshen kwararar mai).

Ga na'urorin transformers 220kV, mun gano cewa dabarun naɗewa masu alaƙatare da kashi-kashi na rabuwa sama da 65-70%, yana inganta rarrabawar ƙarfin lantarki mai ƙarfi sosai, yana rage damuwa akan faifan diski na farko da har zuwa 50% idan aka kwatanta da ƙira na gargajiya.

Nazarin Shari'a: Nasarar Aiwatarwa a cikin Na'urar Canza Wutar Lantarki ta 220kV

Aikinmu na baya-bayan nan wanda ya haɗa da na'urar canza wutar lantarki mai ƙarfin 220kV ya nuna ingancin waɗannan dabarun haɓakawa. Tsarin farko ya nuna yawan ƙarfin filin lantarki mai yawa (har zuwa 9.5kV/mm) a cikin babban gibin rufin da ke tsakanin na'urorin juyawa masu ƙarfin lantarki da ƙananan ƙarfin lantarki, musamman kusa da ƙarshen na'urorin juyawa.

Ta hanyar nazarin FEM na maimaitawa ta amfani da software na musamman (HSSSM), mun aiwatar da cikakken kunshin haɓakawa:

  1. An sake tsara zoben lantarki mai amfani da wutar lantarkitare da ingantaccen lanƙwasa da sanyawa.
  2. Ƙarin zoben kusurwaa ƙarshen lanƙwasa don raba yawan mai da inganta ƙarfin creepage.
  3. An gyara tsarin shingenƙirƙirar ƙananan gibin mai iri ɗaya (6-8mm) maimakon gibin da ya fi girma (12-15mm).

Sakamakon ya kasance abin mamaki: matsakaicin ƙarfin filin ya ragu zuwa 6.2kV/mm (ingantaccen kashi 35%), tare da rarraba filin iri ɗaya a cikin tsarin rufin. Transfomar da aka gyara ta yi nasarar cin dukkan gwaje-gwajen yau da kullun da na nau'i, gami da gwajin ƙarfin wutar lantarki mai jurewa mitar wutar lantarki (460kV na minti 1) da gwajin walƙiya (1050kV), tare da matakan fitarwa na ɗan lokaci ƙasa da 10pC.

La'akari da Masana'antu da Inganci

Ko da mafi kyawun ƙira yana nuna rashin inganci ba tare da ingantaccen sarrafa masana'antu ba. Shirinmu na tabbatar da inganci don rufin transfoma na 220kV ya haɗa da:

  • Sarrafa tsarin ƙididdigayayin ƙera allon bugawa da haɗa kayan aiki.
  • Busar da injin tsotsar ruwa da kuma shafa maihanyoyin da ke tabbatar da kawar da danshi da iskar gas gaba ɗaya waɗanda za su iya fara fitar da wani ɓangare.
  • Taswirar fitarwa ta wani ɓangarea lokacin gwaje-gwajen motsa jiki don gano da gyara duk wani lahani na masana'antu.

Ga na'urorin canza wutar lantarki na 220kV, muna aiwatar da tsauraran ka'idoji na tsafta yayin haɗa tanki da ayyukan tanki, domin ko da ƙananan gurɓatattun abubuwa na iya rage ƙarfin rufin da ke ƙarƙashin manyan filayen wutar lantarki.

Abubuwan da ke Faruwa a Nan Gaba a Fasahar Rufe Ido

Juyin halittar insulation na transformer ya ci gaba da samun ci gaba mai ban sha'awa da dama:

  • Fasaha tagwayen dijitalƙirƙirar kwafi na tsarin rufin gida na kama-da-wane don sa ido kan aiki a ainihin lokaci da kuma kula da hasashen lokaci.
  • Babban sa ido kan yanayinamfani da na'urori masu auna zafin jiki da aka haɗa don bin diddigin ayyukan fitarwa na ɓangare da wuraren zafi a duk tsawon rayuwar aikin na'urar transformer.
  • Ruwan kariya mai kyau ga muhallikamar su esters na halitta waɗanda ke ba da mafi girman wuraren wuta da ingantaccen daidaiton muhalli yayin da suke kiyaye aikin dielectric.

Don aikace-aikacen 220kV, muna da matuƙar farin ciki game da aikace-aikacen koyon injina cikin inganta ƙirar rufi, inda algorithms zasu iya kimanta dubban bambance-bambancen ƙira cikin sauri don gano mafi kyawun tsari waɗanda ke daidaita la'akari da wutar lantarki, zafi, da tattalin arziki.

Kammalawa

Inganta gibin rufin transformer mai ƙarfin 220kV tsakanin coil yana wakiltar ƙalubalen injiniyanci mai zurfi wanda ke buƙatar zurfin ilimin ka'idar dielectric, ƙwarewar kwaikwayo mai zurfi, da ƙwarewar masana'antu. Ta hanyar cikakken nazarin filin lantarki da dabarun haɓakawa da aka yi niyya, za mu iya inganta amincin transformer da tsawon rai sosai.

Hanyarmu ta nuna cewa ƙirar rufin da aka tsara ba wai kawai tana inganta aikin dielectric ba, har ma tana ba da damar ƙaramar na'urorin canza wutar lantarki masu araha da rahusa. Ta hanyar aiwatar da waɗannan dabarun ci gaba, muna isar da na'urorin canza wutar lantarki waɗanda suka wuce ƙa'idodin masana'antu yayin da muke ba wa abokan cinikinmu ingantaccen aminci da fa'idodin mallakar kayayyaki.

Yayin da fasaha ke ci gaba da bunkasa, muna ci gaba da jajircewa wajen haɗa sabbin ci gaba a cikin ƙirar rufin gida, don tabbatar da cewa abokan cinikinmu sun amfana daga ingantattun hanyoyin samar da wutar lantarki da ake da su a kasuwa.

Tuntuɓi ƙungiyar injiniyoyinmu a yaudomin tattauna yadda ƙwarewarmu ta musamman ta ƙirar rufin gida za ta iya haɓaka aiki da amincin ayyukan transfoma na 220kV ɗinku.