Masu canza wutar lantarki, a matsayin kayan aiki na asali a cikin tsarin wutar lantarki, suna yin ayyuka masu mahimmanci ciki har da canza ƙarfin lantarki, daidaita wutar lantarki, da kuma keɓewar wutar lantarki. Aikinsu mai dorewa yana da matuƙar muhimmanci don tabbatar da aminci da ingancin hanyoyin sadarwa na lantarki. Sassan da ke ƙasa suna ba da cikakken bayani game da sarrafa ayyukan transfoma, hanyoyin gano kurakurai na gama gari, da hanyoyin magance matsaloli.

 

 

Shirye-shiryen da Duba Ayyukan Gudanar da Transfoma

 

Kafin a fara aiki da na'urar transfoma, dole ne a yi cikakken bincike domin tabbatar da cewa tana shirye don aiki mafi kyau:

 

Duba Maƙallin da Haɗi: Yi cikakken bincike kan dukkan maƙallan da ke ciki da wajen na'urar transfoma, musamman a wuraren haɗa abubuwa masu mahimmanci kamar tashoshin wayoyi da sandunan bus. Tabbatar da cewa an yi amfani da ƙarfin juyi yadda ya kamata yayin matsewa don hana lalacewar zare, yayin da ake guje wa kamawa da rashin jituwa tsakanin ƙusoshi da goro ke haifarwa.

 

Tabbatar da Shigar da Sassan: Tabbatar da sake shigar da dukkan sassan da aka wargaza yayin jigilar kaya ko shigarwa yadda ya kamata, duba hanyoyin sanyaya na ciki don ganin yanayin da ba shi da tarkace, da kuma tabbatar da rashin kayan aikin da suka rage a cikin ma'ajiyar transfoma.

 

Duba Na'urar Kula da Zafin Jiki: Tabbatar cewa kebul na sarrafawa na masu sarrafa zafin jiki da alamun an karkatar da su daga saman na'urar da sassan da ke rayuwa. Sake tsare su kamar yadda ake buƙata don hana tsangwama.

 

Tsarin Sanyayada Duba Kayan Aiki na Ƙarin Aiki: Tabbatar da cewa fanfunan sanyaya suna aiki yadda ya kamata, na'urorin sarrafa zafin jiki, da kuma tsarin taimako. Musamman tabbatar da alkiblar juyawar fanka don tabbatar da cewa iska tana tafiya sama daga tushe na na'urorin canza wutar lantarki.

 

Gwaje-gwajen Kafin Gudanar da Transformer

 

Domin tabbatar da bin ƙa'idodin ƙira, dole ne a yi waɗannan gwaje-gwajen kafin a fara aikin na'urar canza wutar lantarki:

 

Ma'aunin Juriyar DC: Gudanar da ma'aunin juriyar lanƙwasa a duk wuraren da aka yi amfani da famfo don tabbatar da bin ƙa'idodin ƙira.

 

Ma'aunin Rabon Wutar Lantarki: Tabbatar da daidaitoncanjin ƙarfin lantarkirabo kuma tabbatar da daidaiton nadin ƙungiyar vector ta hanyar duba polarity da jerin matakai.

 

Gwajin Juriyar Rufi: Yi gwajin dielectric tsakanin tsarin tsakiya da mannewa don tabbatar da ingancin rufi.

 

Gwajin Juriya ga Rufin Iska: Auna juriyar rufi na windings don tabbatar da bin ka'idojin aminci na lantarki.

 

Gwajin Juriya da Mitar Wutar Lantarki: Ga masu canza wutar lantarki da aka gyara a filin da suka dawo aiki, za a gudanar da gwajin ƙarfin lantarki mai jurewa da dielectric a kashi 80% na matakin ƙarfin lantarki na masana'anta na asali, bisa ga buƙatun IEC 60076-3 Sashe na 10.

 

Gargaɗi don aminci wajen aiki da na'urorin canza wutar lantarki

 

Duba Tsarin Gina Ƙasa: Yi cikakken bincike kan tsarin ginshiƙai bayan an shigar da su domin tabbatar da ingancin aikinsu.

 

Shingen Tsaro: Na'urorin transfoma marasa kariyar rufewa za su kasance sanye da shingen keɓewa don hana hulɗa kai tsaye da sassan da ke rayuwa da kuma rage haɗarin kamuwa da wutar lantarki.

 

Aiki Daga Ma'aikata Masu Inganci: Shigarwa, sanyawa, da kuma kula da na'urorin lantarki masu canzawa za a yi su ne kawai ta hanyar ƙwararrun masu lasisi don tabbatar da bin ƙa'idodin aiki da ka'idojin aminci.

 

Gargaɗi Don Sanya Na'urar Canza Wutar Lantarki

 

Kunna Tsarin Kula da Zafin Jiki: Kafin a kunna wutar lantarki, a daidaita kuma a gwada na'urar sarrafa zafin jiki ko na'urar nuna zafin jiki don tabbatar da aiki yadda ya kamata.

 

Tsarin Samar da Makamashi: Rufe na'urorin da ke karya da'ira tare da na'urar canza wutar lantarki ba tare da wani kaya ba. Kunna na'urar sake kunna wutar lantarki ta gaggawa yayin samar da wutar lantarki don rage tasirin wutar lantarki ta inrush.

 

Ƙara nauyi a hankali: Bayan an fara aiki, ya kamata a ƙara nauyin a hankali a kuma sa ido kan duk wani sauti ko girgiza da ba a saba gani ba don guje wa ƙaruwar nauyi kwatsam.

 

Tsarin Rage Danshi: Ga masu canza wutar lantarki da suka fuskanci zafi fiye da kashi 80% na RH.

 

Kurakuran Transformer da Ayyukan Gyara

 

Lalacewar dumama fiye da kima: Wannan ya haɗa da zafi fiye da kima da kuma yawan zafin jiki gaba ɗaya. Duba yanayin fitarwa, wutar lantarki, da yanayin watsar da zafi.

 

Kurakuran fitar da ruwa: Yana iya bayyana a matsayin wani ɓangare na fitar da ruwa, fitar da ruwa, ko fitar da tartsatsin wuta; galibi yana da alaƙa da matsalolin rufin.

 

Lalacewar rufi: Kamar lalacewar rufi ko lalacewar aikin rufi; dole ne a duba kayan rufi da suka lalace cikin gaggawa kuma a maye gurbinsu.

 

Sauran kurakurai: Har da hayaniya mara kyau, matsalar kariya, yoyon mai, da sauransu.

 

Hanyoyin Gano Laifi‌:

 

Dubawa ta gani‌: Duba kwararar kaya, canjin launin mai, da kuma bayyanar waje don ganin abubuwan da ba su dace ba (misali, malalar mai, canza launi).

 

Kula da ji‌: Saurari sautuka marasa kyau yayin aiki (misali, ƙarar sauti mara daidai, ƙara, ko sautin hayaniya).

 

Ma'aunin Wutar Lantarki‌: Auna juriyar DC mai matakai uku da juriyar rufi don tantance ko ƙimar ta faɗi cikin kewayon da aka saba.

 

 

Gyaran Kuskuren Aikin Rufi‌

 

Rage aikin rufin abu ne da ya zama ruwan dare gama gari ga masu canza wutar lantarki, musamman a yanayin danshi. Ya kamata a gudanar da gwajin juriyar rufin a ƙarƙashin yanayi mai dacewa, tare da waɗannan ƙimar da aka saba amfani da su:

 

HV zuwa LV da ƙasa: ≥ 300 M Ω (10kV), ≥ 1000 M Ω (35kV).

HV zuwa ƙasa: ≥100 MΩ.

Don ‌core/accessories to ground‌, duba takardun masana'anta.

 

Idan na'urar transformer ta nuna shigar danshi ko kuma danshi (misali, digo-digo da ake gani a saman resin epoxy ko abubuwan da ke cikin core), ana buƙatar busarwa nan take don dawo da ingancin rufin, ba tare da la'akari da ƙimar juriyar rufin da take da ita a yanzu ba.

 

 

Tsarin Rage Hayaniya Mai Sauti Mai Sauri na Transformer

 

Aikin transfoma na yau da kullun zai samar da sautin ƙara wanda ya bambanta da nauyin da aka ɗora. Idan akwai wani sauti mara kyau, ana buƙatar ƙarin bincike:

 

Sassautawa daga tsakiya: Yana haifar da ƙarar ƙara ko ƙara saboda rashin tsaro ko ƙarancin ƙarfin ƙwanƙwasa.

 

Ba a gina harsashi ba: Yana haifar da sautin fitar da iska daga taruwar lantarki tsakanin tsakiya da tanki.

 

Lalacewar hulɗar maɓalli‌: Yana haifar da ƙara ko ‌ƙara daga ‌ƙara a cikin na'urorin canza famfo ko gidajen bas.

 

Fitar da gubar/lantarki: Yana fitar da ‌awon sauti daga lalacewar rufin da ke cikin yankunan da ke da ƙarfin lantarki mai yawa.

 

Gurɓatattun bushings‌: Yana haifar da fitar da sinadarin corona saboda tarin mai/ƙwaya a saman fata.

 

Gyaran Matsalolin Kula da Zafin Jiki‌

 

Rashin Kunnawa: Duba samar da wutar lantarki, fis, haɗin tashoshi, da kuma yanayin maɓallan.

 

Babu Nunin Zafin Jiki: Duba haɗin firikwensin da juriya.

 

Bambancin Zafin Jiki: Duba shigar da na'urori masu auna firikwensin da hanyoyin tsangwama.

 

Rashin Sadarwa: Duba layin sadarwa kuma tuntuɓi tallafin fasaha na mai samar da kayayyaki.

 

Maganin Rage Rashin Daidaiton Wutar Lantarki Mai Mataki Uku

 

Rashin daidaiton ƙarfin lantarki na matakai uku galibi yana faruwa ne sakamakon lahani na ƙasa ko rashin daidaiton kaya. Mafita sun haɗa da:

 

Tsarin Gina Ƙasa Mai Ma'ana da yawa don Rage Asarar Layi Mai Tsaka-tsaki‌ Aiwatar da ginshiƙin ƙasa mai ma'ana da yawa a cikin hanyoyin rarraba wutar lantarki mai ƙarancin wutar lantarki don rage asarar wutar lantarki mai tsaka-tsaki ta hanyar inganta hanyoyin dawowa na yanzu da rage juriya.

 

Na'urar Canzawa Mai Mataki Ɗaya Aiki: Yi amfani da na'urorin canza wutar lantarki guda ɗaya don yankunan da ke da manyan lodi na lokaci ɗaya (misali, yankunan zama) don ware kwararar wutar lantarki marasa daidaito da kuma hana tsangwama mai jituwa.

 

Kulawa da Daidaita Lodi‌: Gudanar da auna nauyi lokaci-lokaci ta amfani da mitoci masu matsewa don auna karkacewar halin yanzu tsakanin matakai.

 

Maganin Bambancin Launi da Yaɗuwar Man Fetur

 

‌Duhun Mai‌: Duhun mai (misali, launin ruwan kasa ya koma launin ruwan kasa/baƙi) yana nuna ‌shanye danshi‌ da kuma lalacewar iskar oxygen‌, wanda ke haifar da raguwar ƙarfin dielectric da kuma ƙaruwar acidity‌. Sauya man da ya lalace da sauri don hana tsufa cikin sauri na rufin da kuma yuwuwar gazawar kayan aiki.

 

Zubar da Mai: Tantance ko za a ci gaba da aiki da kuma shirya gyara bisa ga yanayin zubar da mai, ko kuma a rufe nan take a sake cika mai

 

A ƙarshe, Ingantaccen aikin na'urorin lantarki shine ginshiƙin aminci ga tsarin wutar lantarki. Ta hanyar dubawa mai kyau, gano kurakurai/mafita cikin gaggawa, da kuma kulawa mai kyau, ana iya tsawaita rayuwar na'urorin lantarki yadda ya kamata, rage yawan lalacewa, da kuma tabbatar da aminci/ingancin tsarin wutar lantarki.