Gabatarwa;

A aikace-aikacen transformer mai matsakaicin ƙarfi da ƙarfin lantarki, tsarin riƙe mai yana da matuƙar muhimmanci ga kariyar muhalli, bin ƙa'idodi, da amincin aiki. A JZP, mun ƙware wajen tsara hanyoyin hana mai ƙarfi waɗanda aka tsara su bisa ga buƙatun musamman na transformers na masana'antu da na masu amfani. Wannan jagorar ta fayyace mahimman abubuwan da za a yi la'akari da su da hanyoyin da za a bi don tantance girman da ya dace na tsarin hana mai na transformer, tare da tabbatar da daidaito da ƙa'idodin ƙasa da ƙasa da buƙatun takamaiman ayyuka.

Muhimman Abubuwan da ke Shafar Girman Tsarin Kariya;

 

Ƙarar Man Transfoma;

 

Babban Ka'ida: Tsarin tsarewa dole ne ya dace da Kashi 100% na mafi girman ƙarfin man fetur na na'urar transformera cikin yanayi na yau da kullun da kuma Kashi 110% a lokacin yanayin gobara(gami da ruwan kashe gobara da ruwan sama)

 

Misali Lissafi:

 

Na'urar transformer mai karfin 110 kV mai karfin tan 30 (≈34 m³) tana buƙatar adadin da za a iya amfani da shi wajen adana man fetur. 37.4 m³(34 m³ × 1.1) don cika ƙa'idodin tsaron gobara.

 

Nassoshi Masu Ka'idoji:

 

GB50060-2008ya umarci tsarin tsarewa don Na'urar Canza Wutar Lantarki ta Wajemai ƙarfin mai ≥1,000 kg dole ne ya riƙeKashi 60% na girman tankin mafi girmaidan an aiwatar da raba mai da ruwa.

 

Yanayi na Musamman na Wurin;

 

 

Shigarwa na Cikin Gida da na Waje:

 

Na'urorin canza wutar lantarki na cikin gida (misali, a tashoshin samar da wutar lantarki) galibi suna buƙatar ƙaramin tsari saboda yanayin da ake sarrafawa, yayin da tsarin waje dole ne ya yi la'akari da ruwan sama da kuma yadda ƙasa ke shiga.

 

Tsaftace Tsaron Gobara:

 

Kula da mafi ƙarancin nisan mita 1.5tsakanin transformers da bangon da ke ƙonewa, da kuma Mita 1 bayan gefunan transfomadon watsa ruwan wuta

 

Abubuwan da suka shafi fannin ƙasa da muhalli;

 

Ƙarfin Ɗaukan Ƙasa: Kimanta nau'in ƙasa (misali, yumbu, tsakuwa) don tantance daidaiton tushe da buƙatun magudanar ruwa

 

Yawan Ruwan Sama: Don tsarin waje, ƙididdige gudummawar ruwan sama ta amfani da bayanan yanayi na gida (misali, 100 mm/hr ga yankunan wurare masu zafi).

 

 

Tsarin Girma Mataki-mataki;

 

Ƙayyade Matsakaicin Ƙarar Mai;

 

Yi bitar zane-zanen fasaha na na'urar canza wutar lantarki don gano mafi girman ƙarfin mai (misali, lita 10,000 ga na'urar MVA 60).

 

Aiwatar da Bukatun Dokoki;

 

Yarjejeniyar SPCC: Ga shigarwar Amurka, bi ƙa'idar EPA 110% (ƙarfin mai + 10% kyauta)

 

Ma'aunin Sinanci:

 

GB50053-2013: Yana buƙatar kariyar kashi 20% ga na'urorin canza wutar lantarki na cikin gida waɗanda ke da mai ≥100 kg, wanda hakan ke ƙaruwa zuwa kashi 100% idan magudanar ruwa ba ta da amfani.

 

Lissafa Ƙarar Ƙuntatawa;

 

Tsarin dabara:

 

A cikinjimilla=(A cikinmai×1.1)+(A cikinruwa × 0.35)

 

V_water: Girman ruwan wuta (fadin saman × saurin kwarara × tsawon lokaci).

 

0.35: Kashi mara inganci na abubuwan da aka cika da tsakuwa (kashi 40% na porosity)

 

Tsarin Canzawa da Yawa;

 

 

A tattara yawan mai don na'urorin transformers masu tarin yawa sannan a ƙara kashi 20% na rage amfani da mai don faɗaɗawa nan gaba.

 

 

Mafi kyawun Ayyuka don Tsarin Tsarin Rigakafi;

 

Zaɓin Kayan Aiki;

 

Siminti Mai Ƙarfafawa: An fi so don amfani a cikin gida saboda juriyar wuta da dorewa.

 

Layin Geomembrane: Yi amfani da layukan HDPE a wuraren waje don hana zubewa cikin ƙasa

 

Bayanin Tsarin Tsakuwa;

 

Kauri: ≥250 mm.

 

Girman Dutse: diamita na 50–80 mm don mafi kyawun ramuka da rage gobara

 

Rabawar magudanar ruwa da Mai da Ruwa;

 

 

Sanya bututun da suka huda rami masu diamita ≥150 mm da kuma allon bakin karfe don tace gurɓatattun abubuwa.

 

Juriyar Girgizar Ƙasa da Iska;

 

Tsarin kusoshin anga don juriya 0.4 ma'aunin gogayya mara motsida nauyin da ya shafi yankin girgizar ƙasa

 

 

Kammalawa;

Zaɓar girman man transformer da ya dace yana buƙatar yin nazari mai zurfi game da yawan mai, ƙa'idodin ƙa'idoji, da yanayin wurin. A JZP, muna amfani da kayan aikin injiniya na zamani da mafi kyawun hanyoyin masana'antu don samar da tsarin hanawa wanda ke ba da fifiko ga aminci, bin ƙa'idodi, da ingancin aiki. Yi haɗin gwiwa da mu don tabbatar da matsakaicin ku da babban matakin kariya.Masu Canza Wutar Lantarki ana kare su daga ɓuɓɓugar ruwa, gobara, da kuma haɗarin muhalli.