Na'urar Canzawa Mai Nitsewa Na'urorin juyawa suna da matuƙar muhimmanci a tsarin rarraba wutar lantarki, waɗanda aka tsara don canja wurin makamashin lantarki yadda ya kamata yayin da ake tabbatar da aminci da dorewa. A ƙasa akwai cikakken bayani game da tsarinsu, kayansu, da ƙa'idodin aiki, waɗanda aka haɗa daga ƙa'idodin masana'antu da ƙayyadaddun fasaha.
An haramta zafin saman transformer da aka nutsar da mai ya wuce digiri 95 na Celsius, gabaɗaya an hana shi ya wuce digiri 85 na Celsius, zaɓin na'urar juyawa ta janar na kayan rufin aji A, matsakaicin zafin da aka yarda da kayan rufin shine 95 ~ 105 ° C, a cikin ƙayyadaddun bayanai na dumama transformer na China an dogara ne akan zafin aiki na 40 ° C a matsayin daidaitaccen, na'urar juyawa ta matsakaicin zafin iskar gas da aka haɗa a cikin digiri 65 Celsius. Hawan zafin saman mai zuwa gas ɗin an sanya shi daidai a digiri 55 na Celsius, don haka na'urar juyawa da ke ɗauke da tsakiyar transformer an haɗa ta cikin haɓakar zafin mai a digiri 10 na Celsius.
Idan zafin saman na'urar transformer ya kai 85 ° C, zafin lanƙwasa shine 95 ° C; Idan zafin saman ya kai 95 ° C, zafin lanƙwasa ya kai 105 ° C, wanda ya kai matsakaicin zafin da aka yarda da shi na kayan lanƙwasa. Zafin da ya yi yawa zai hanzarta tsufan kayan lanƙwasa, ya hanzarta lalacewar man transformer, ya cutar da rayuwar sabis na Na'urar Canza Rarrabawas, har ma yana haifar da haɗarin tsaro.
Tsarin zagayawa mai ƙarfi mai sanyaya iska, mai canza wutar lantarki mai zafi 75℃ 35℃; Tsarin zagayawa na halitta na mai, kariya daga zafin jiki mai yawa, mai canza wutar lantarki mai sanyaya iska, zafin saman gabaɗaya bai dace da shi ba sau da yawa fiye da 85°C, zafi mai zafi ba zai wuce 95°C ba zai iya wuce 55°C ba, idan aka same shi a cikin aiki na ƙimar iyaka ya wuce buƙatun, ya kamata ya ba da rahoton jadawalin samarwa nan da nan, amfani da matakan kariya na iyaka.
1. Ma'ana da Babban Aiki
Na'urorin juyawa masu nutsewa da mai sun ƙunshi na'urorin jan ƙarfe ko aluminum da aka ɗaure a kusa da tsakiyar ƙarfe mai laminated silicon. Waɗannan na'urorin juyawa suna nutsewa gaba ɗaya cikin man shafawa, wanda ke aiki da dalilai biyu: rufin lantarki da kuma sarrafa zafi. Na'urorin juyawa suna canza shigarwar wutar lantarki mai ƙarfi zuwa fitarwa mai ƙarancin wutar lantarki (ko akasin haka) ta hanyar shigar da wutar lantarki, wanda ke ba da damar watsa wutar lantarki lafiya a fadin grids.
2. Haɗaɗɗen Kayan Aiki
Kayan aiki mai sarrafawa:
Tagulla: Ana amfani da shi sosai don naɗe-naɗen wutar lantarki mai ƙarfi saboda ƙarfinsa mai kyau da kuma ƙarfin injina. Naɗe-naɗen wutar lantarki mai ƙarancin ƙarfin lantarki (≤500 kVA) galibi suna ɗaukar tsarin silinda mai layi biyu, yayin da manyan ƙarfin lantarki (≥630 kVA) suna amfani da tsarin helix biyu ko huɗu-huɗu don inganta rarrabawar yanzu
Aluminum: A wasu lokutan ana amfani da shi don aikace-aikace masu sauƙin tsada, kodayake ba shi da inganci kamar jan ƙarfe.
Rufin rufi:
Kayan da ke da juriya sosai (misali, resin epoxy, takarda mai tushen cellulose) suna ware madaukai daga tsakiya da juna.
Rufin rufi mai layuka da yawa yana hana gajerun da'irori a ƙarƙashin matsin lamba na zafi ko nakasa ta injiniya.
3. Tsarin Gine-gine
Tsarin Gyaran Wuta:
Na'urar juyawa mai ma'ana (Zirki): An saba da ita a cikin na'urorin juyawa masu matakai uku, inda ake sanya na'urorin juyawa masu ƙarancin ƙarfin lantarki a cikin na'urorin juyawa masu ƙarfin lantarki mai ƙarfi don rage kwararar ɓuɓɓuga.
Na'urar Rage Rauni (Helical): Ana amfani da ita don amfani da wutar lantarki mai ƙarfi, tana da layuka masu laushi don rage asarar wutar lantarki.
Haɗin Sanyaya:
Na'urorin haɗi sun haɗa da bututun mai don isar da watsawar zafi ta hanyar amfani da na'urar tura iska ta halitta ko ta tilasta.
Tankunan mai na roba sun maye gurbin na'urorin adana mai na gargajiya, wanda ke ba da damar faɗaɗa mai a yanayin zafi yayin da ake kiyaye muhalli mai rufewa.
4. Inganta Aiki
Tsarin Asara Mai Ƙaranci:
Amorphous Alloy Cores: Rage asarar hysteresis da eddy current (misali, na'urorin canza wutar lantarki na jerin S11-M suna samun raguwar asara da kashi 30% fiye da tsofaffin samfura)
Ƙungiyar Haɗin Dyn11: Yana rage karkacewar jituwa da inganta ingancin wutar lantarki ta hanyar rage kwararar harmonics na uku
Juriyar Gajeren Zagaye:
Maƙallan lanƙwasa masu ƙarfi da dabarun lanƙwasa masu karkace suna ƙara kwanciyar hankali a lokacin da ake fuskantar matsala.
Na'urorin numfashi na silica gel da kuma Buchholz relays suna sa ido kan matsalolin danshi da kwararar mai.
5. Aikace-aikace da Kulawa
Yanayin Turawa:
Tashoshin samar da wutar lantarki na masana'antu, hanyoyin samar da wutar lantarki na birane, da kuma tsarin makamashi mai sabuntawa (misali, gonakin iska).
Ƙarfin da aka ƙima ya kama daga 50 kVA zuwa 25,000 kVA, tare da ƙarfin lantarki har zuwa 35 kV
Ayyukan Gyara:
Samfuran mai na yau da kullun da kuma nazarin iskar gas da aka narkar (DGA) don gano lalacewar rufin.
Hoton zafi don gano wuraren da ke da zafi a cikin maɓuɓɓugan ruwa.
6. Sabbin abubuwa a Fasahar Winding
Rufewar Vacuum: Yana kawar da iska yayin ƙera ta, yana inganta ingancin rufin
Kulawa Mai Wayo: Na'urori masu auna firikwensin da ke aiki da IoT suna bin diddigin yanayin zafi da ƙarfin kaya a ainihin lokaci.