Gabatarwa

A cikin tsarin wutar lantarki mai ƙarfin lantarki mai yawa, hanyar amfani da na'urar juyawa mai tsaka-tsaki a matsayin tushen ƙasa muhimmin abu ne da ke tasiri ga amincin tsarin, aminci, da kwanciyar hankali. Ga tsarin wutar lantarki na 110kV, zaɓin hanyar amfani da na'urar juyawa mai tsaka-tsaki a matsayin tushen ƙasa kai tsaye yana shafar matakan rufin kayan aiki, kariyar ƙarfin lantarki mai yawa, tsarin kariyar relay, da amincin samar da wutar lantarki. A China, tsarin 110kV yawanci yana amfani da hanyar ƙasa mai inganci kaɗan, inda wasu wuraren da ba su da tsaka-tsaki na transformer suna kan tushe kai tsaye yayin da wasu kuma ba su da tushe, da nufin iyakance kwararar wutar lantarki ta mataki ɗaya yayin da ake hana barazanar wuce gona da iri.

Wannan labarin yana nazarin halaye, fa'idodi, da iyakokin hanyoyin samar da wutar lantarki mai ƙarfin lantarki 110kV daban-daban, yana bincika dabarun tsari mafi kyau na kariya, kuma yana gabatar da sabbin dabarun ci gaba a nan gaba.

Hanyoyi 1 Masu Mahimmanci na Tsarin Ƙasa don Masu Canza Wutar Lantarki 110kV

1.1 Gina ƙasa kai tsaye

Gina tushe kai tsayeYana nufin haɗin kai tsaye na wurin tsaka-tsaki na transformer zuwa ƙasa. Wannan hanyar tana gyara ƙarfin wurin tsaka-tsaki yadda ya kamata, tana tabbatar da cewa a lokacin matsalar ƙasa mai mataki ɗaya, ƙaruwar ƙarfin lantarki na matakin da ba shi da laifi bai wuce sau 1.4 na ƙarfin lantarki na matakin ba. Wannan yana taimakawa rage buƙatun rufin kayan aiki da rage farashi.

Duk da haka, babban hasara shine babban ƙarfin wutan lantarki na ƙasa guda ɗaya mai ƙarfi(har zuwa dubunnan amperes), wanda zai iya shafar ƙarfin katsewar na'urar fashewa da kwanciyar hankali na tsarin. Saboda haka, galibi ana amfani da ƙasa kai tsaye a cikin tsarin wutar lantarki na 110kV da mafi girma inda ake buƙatar cire kurakurai cikin sauri.

1.2 Ba a gina ƙasa ba

A cikin wani tsarin da ba a gina shi ba, wurin da ba shi da tsaka tsaki na transformer yana da kariya daga ƙasa. Idan matsalar ƙasa ta faru a mataki ɗaya, matsalar wutar lantarki ƙarami ne (galibi wutar lantarki mai ƙarfin tsarin), wanda ke ba tsarin damar ci gaba da aiki na ɗan gajeren lokaci (yawanci har zuwa awanni 2). Wannan yana ƙara girma sosai. Ingancin samar da wutar lantarki.

Duk da haka, a cikin tsarin da ba a gina ƙasa ba, matsalolin ƙasa na mataki ɗaya na iya haifar da ƙarfin lantarki na matakin da ba shi da laifi ya tashi zuwa matakin ƙarfin lantarki na layi. Idan rufin ya yi rauni, wannan na iya haifar da lalacewa, yana ƙaruwa zuwa matsala daga mataki zuwa mataki. Bugu da ƙari, tushen baka mai katsewa na iya haifar da ƙarfin lantarki na baka, wanda ya kai sau 3–3.5 na ƙarfin lantarki na matakin, wanda hakan ke barazana ga rufin transfoma.

1.3 Yin amfani da ƙasa ta hanyar ƙaramin impedance

Domin daidaita fa'idodi da rashin amfanin tsarin ƙasa kai tsaye da tsarin da ba a gina shi ba, Hanyar ƙasa ta impedanceana amfani da shi sau da yawa. Wannan ya haɗa da yin amfani da ƙasa ta hanyar ƙaramin juriya ko ƙaramin amsawa.

  • Ƙananan Juriya na Ƙasa: Yana iyakance wutar lantarki zuwa ɗaruruwan amperes, yana rage tasirin tsarin yayin da har yanzu yana ba da damar yin aiki cikin sauri na kariya. Wannan hanyar tana danne ƙarfin lantarki mai yawa kuma ta dace da hanyoyin sadarwa masu amfani da kebul tare da manyan kwararar wutar lantarki.
  • Ƙaramin Gina Gine-gine: Zai iya daidaita ƙarfin wutar lantarki na tsarin ta hanyar amfani da wutar lantarki mai inductive, wanda ke rage yuwuwar sake yin arc reignition. Sau da yawa ana ɗaukar wannan hanyar a matsayin hanyar ƙasa mai ramawa.

Yin amfani da ƙasa ta hanyar ƙaramin impedance yana haɗa fa'idodin tsarin kai tsaye da na ƙasa, yana ba da damar rage ƙarfin lantarki da kuma ingantaccen ƙarfin wutar lantarki. Ana amfani da shi sosai a cikin tsarin 110kV, musamman waɗanda ke da kwararar wutar lantarki mai ƙarfi ko kuma waɗanda ke buƙatar ingantaccen ƙarfin lantarki.

Tsarin Kariya 2 don Maki Mai Tsaka-tsaki na Transformer 110kV

2.1 Barazanar Ƙarfin Wutar Lantarki

Matsayin rufin da ke tsakanin na'urar transformer 110kV yawanci yana da ƙarfi sosai. mai rufewa mai rabin-ruwa, tare da ƙimar ƙarfin lantarki mai jurewa kashi ɗaya bisa uku kawai na ƙarshen layin. Wannan yana sa wurin tsaka-tsaki ya zama mai sauƙin lalacewa ga lalacewar ƙarfin lantarki. Nau'ikan ƙarfin lantarki na farko sun haɗa da:

  • Ƙarfin wutar lantarki na Mitar Wutar Lantarki: Tasowa daga sauya layi, gajerun da'irori marasa daidaituwa, ko asarar kaya kwatsam.
  • Ƙarfin wutar lantarki mai yawa: Yana faruwa ne sakamakon juyawar iska sakamakon hulɗar da ke tsakanin abubuwan da ke haifar da inductive da capacitive yayin ayyukan tsarin ko kurakurai.
  • Sauya Ƙarfin Wutar Lantarki: Sakamakon juyawar makamashin maganadisu da na lantarki yayin buɗewa ko rufewar na'urorin fashewa na da'ira.
  • Ƙarfin Wutar Lantarki Mai Ƙarfi: An haifar da walƙiya, wadda ke da girman girma da kuma ɗan gajeren lokaci.

2.2 Na'urorin Kariya Na Yau Da Kullum

Don kare wurin da ba shi da tsaka tsaki na transformer, ana amfani da waɗannan na'urorin kariya:

  • Masu Kama Ruwa: Waɗannan suna iyakance ƙarfin walƙiya da wasu ƙarfin juyawa. Duk da haka, masu hana ƙaruwar wutar lantarki na yau da kullun ba su isa ga ƙarancin matakin kariya na maki masu tsaka tsaki na transformer 110kV ba, wanda hakan ke sa zaɓi ya zama ƙalubale.
  • Gibin Warewa: Waɗannan suna kare daga mitar wutar lantarki da kuma ƙarfin lantarki mai ƙarfi. Lokacin da ƙarfin lantarki ya wuce gona da iri, rata ta lalace, tana rushe wurin tsaka-tsaki don iyakance hauhawar wutar lantarki. Wani koma-baya shine wahalar daidaita tazara daidai, wanda zai iya haifar da rashin daidaiton kariya.
  • Haɗin layi ɗaya na Mai ɗaurewa da Rata: Wannan wata hanya ce ta kariya da ake amfani da ita sosai. Mai hana ƙarar wutar lantarki yana kula da ƙarfin walƙiya, yayin da rata ke magance mitar wutar lantarki da ƙarfin lantarki mai ƙarfi. Rata kuma tana kare mai hana ƙarar wutar lantarki daga yawan ƙarfin wutar lantarki mai ƙarfi wanda zai iya haifar da gazawarsa. Wannan hanyar tana ba da fa'idodi masu dacewa.

2.3 Tsarin Kariyar Relay

Kariyar relay don wurin da ke tsaka tsaki na transformer 110kV ya ƙunshi fannoni masu zuwa:

  • Kariyar Wutar Lantarki Sifili: Ga masu canza wutar lantarki da aka gina kai tsaye, ana tsara kariyar wutar lantarki mai tsari sifili don cire lahani cikin sauri a ƙasa. Yawanci ana raba kariyar zuwa sassa, tare da jinkirin lokaci na ɗan lokaci don gano lahani da kuma jinkirin lokaci na dogon lokaci don karkatar da dukkan bangarorin na'urar.
  • Kariyar Wutar Lantarki Sifili da Kariyar Yanzun Gap: Ga na'urorin transformers marasa tushe, ana saita kariyar ƙarfin lantarki mai sifili da kariyar wutar lantarki mai gibi. Lokacin da matsalar ƙasa ta sa tsarin ya rasa wurin ƙasa, wanda ke haifar da ƙaruwar ƙarfin lantarki mai tsaka-tsaki, gibin zai lalace. Kariyar wutar lantarki mai gibi ko kariyar wutar lantarki mai sifili yana aiki tare da jinkirin lokaci (0.3–0.5s) don karkatar da na'urar transformer a kowane gefe.
  • Daidaito kan Kariyar Ajiya: Domin tabbatar da zaɓi, dole ne a daidaita jinkirin lokacin kariya sifili. Misali, jinkirin lokacin kariya ta madadin akan na'urar transformer ya kamata ya fi tsayi fiye da na kariyar layin da yake goyan baya.

Shawarwari 3 na Ingantawa da Nazarin Shari'a

3.1 Iyakokin Hanyoyin Gargajiya

A lokacin amfani da masu riƙewa a tsaye tare da gibbaabu ne gama gari, wannan hanyar tana da wasu matsaloli:

  • Wahala a Zaɓin Mai Kamawa na Surge: Yana da ƙalubale a sami daidaitattun masu riƙe wutar lantarki waɗanda suka cika buƙatun ƙarfin lantarki mai ci gaba da aiki da kuma ƙarfin lantarki mai ƙarancin walƙiya don wuraren da ba su da tsaka tsaki na transformer 110kV.
  • Kalubale a Tsarin Gibi: Ƙarfin wutar lantarki na rushewar gibin iska yana fuskantar watsewa, wanda hakan ke sa ya zama da wahala a daidaita aikin gibin daidai don yanayin "ɓacewar ƙasa" da kuma "tare da ƙasa".
  • Rikicewar Kariyar Relay: Kariya daga "asarar ƙasa" (kamar wuce gona da iri na sifili da kuma kariyar wuce gona da iri ta hanyar gibin) na iya yin lahani, wanda ke buƙatar ƙarin ƙa'idodin toshewa, wanda ke ƙara rikitarwa da rage aminci.

3.2 Fa'idodin yin amfani da ƙasa ta hanyar ƙaramin amsawa

Bincike da aiki sun nuna cewa ƙasa wurin tsaka-tsaki ta hanyar ƙaramin amsawayana ba da fa'idodi masu yawa fiye da hanyoyin gargajiya na ƙasa na ɓangare:

  • Rage Bukatun Matakan RufewaBayan amfani da ƙaramin tushe na reactance, za a iya rage matakin rufin wurin da ba shi da tsaka tsaki na transformer daga 35kV zuwa 20kV, wanda hakan ke kawar da buƙatar masu ɗaurewa da gibin da ke tattare da su da kuma sauƙaƙa tsarin kariya.
  • Yanayin Ƙasa Mai Haɗaka: Wannan hanyar tana kawar da faruwar tsarin da ba shi da tushe, wanda ke ba da damar sauƙaƙewa ko rashin kariya mai alaƙa, ta haka yana ƙara aminci.
  • Rike Fa'idodi: Yana kiyaye fa'idodin yin amfani da ƙasa kaɗan, kamar kariyar sifili mai sauƙi da aminci, yayin da yake iyakance kwararar wutar lantarki mai matakai ɗaya.

3.3 Nazarin Nazarin Lamura

Misali shine canjin tashar samar da wutar lantarki mai karfin 110kV. Tsarin asali ya yi amfani da mai riƙe da ƙararrawa a layi ɗaya da ratadon kariyar maki tsaka-tsaki. Duk da haka, bayan amfani da ƙaramin tushe na reactance, an rage buƙatar matakin kariya na wurin tsaka-tsaki na transformer, an sauƙaƙa na'urorin kariya, kuma an inganta amincin aiki. Lissafi ya nuna cewa juriyar ƙasa na iya iyakance wutar lantarki zuwa ƴan amperes ɗari, kuma ana iya daidaita kariyar sifili cikin sauƙi.

Wani lamari kuma ya shafi matsala a tashar samar da wutar lantarki mai karfin 110kV inda matsalar kasa mai mataki daya ta wucin gadi a layin da ke shigowa ta haifar da lalacewar gibin maki mara tsaka tsaki da kuma gazawar na'urar transfoma. Bincike ya nuna cewa duk da cewa matsalar layin wucin gadi ce, amma Ra'ayoyin da aka samu daga yawan injunan asynchronousa gefen kaya ya samar da makamashi ga baka, yana riƙe da matsalar. Wannan yana nuna cewa ga masu canza wutar lantarki masu manyan nauyin mota (masu daidai), cikakken kariyar maki tsaka-tsaki, gami da overcurrent na sifili, current na gap, da kuma kariyar ƙarfin lantarki na sifili, yana da mahimmanci a lokacin ƙirar.

4 Kammalawa da Hangen Nesa

Zaɓin hanyar samar da na'urar lantarki mai ƙarfin lantarki 110kV da kuma tsarin kariyarsa aiki ne mai fannoni da dama wanda ke buƙatar la'akari da tsarin tsarin, halayen kaya, da buƙatun aminci. Duk da cewa hanyar samar da na'urar lantarki mai ƙarfi tare da masu ɗaurewa da gibin da aka saba gani, tana fuskantar ƙalubale wajen zaɓar na'urori da daidaita su. hanyar ƙasa mai ƙara yawan amsawayana ba da wata hanya mai kyau, wadda za ta iya rage buƙatun rufi, sauƙaƙa kariya, da kuma inganta aminci.

Yanayin ci gaba na gaba zai mayar da hankali kan waɗannan fannoni:

  • Amfani da Sabbin Na'urori: Kamar gibin da aka haɗa ko gibin da za a iya sarrafawa da ake amfani da shi a layi ɗaya da masu ɗaurewa, yana ƙara aminci da daidaiton kariya.
  • Fasahar Kariyar Dijital: Amfani da kariyar da aka dogara da kwamfuta ta hanyar microcomputer tare da ingantattun algorithms (misali, gano siffar raƙuman ruwa, nazarin jituwa) don inganta hankali da amincin kariyar lahani ta ƙasa.
  • Daidaitawa da Daidaitawa: Haɓaka kayan aikin kariya na ma'auni mai daidaito da na zamani don sauƙaƙe ƙira da kulawa.

A taƙaice, inganta hanyar samar da wutar lantarki mai matsakaicin ƙarfin lantarki na 110kV da kuma tsarin kariya yana da matuƙar muhimmanci don inganta aminci, aminci, da kuma tattalin arzikin tsarin wutar lantarki. Tare da ci gaban fasaha, ana sa ran mafita masu wayo da inganci za su fito kuma su sami aikace-aikace a ko'ina.